UPS 300 (260-0251) Specifications Faxback Doc. # 5744 Battery type: Maintenance-free, sealed lead-acid Approval: Approved as "dry cell: for air shipment by Department of Transportation and IATA Voltage/Capacity: 12V, 6.5 Amp-hr Recharge time: 6 hours typical Dimensions: 6.25 in. x 3.75 in x 13.75 in. 15.8 cm. x 9.5 cm. x 34.9 cm. Unit Weight: 18 lbs. 8.2 kg. Shipping Weight: 21 lbs. 9.5 kg. Temperature: Operating: 55 to 85 degrees F (13 to 30 degrees C) Storage: -40 to 14\50 degrees F (-40 to 66 degrees C) Storage of batteries at high temperatures severely shortens battery life. Battery ratings are at 77 degrees F (25 degrees C). TYPICAL SYSTEM BACKUP TIME Work Stations: 20 min 286 Floppy: 15 min 386 File Server: 10 min typical transfer time: 2 milliseconds typical transfer points: 102 VAC (low) 132 VAC (high) Output receptacles: 3 NEMA 5-15R Panel indicators: 1-LED-Output Voltage Audible alarm: Beeps for inverter operation (every 8 sec.) ELECTRICAL Input voltage: 120 VAC, single phase Input frequency: 60 Hz Input current: 4.0 A (maximum) Input connection: Line cord with NEMA 5-15P Input protection: 4 A, 250 V, slow-blow fuse Transient protection: Tested to IEEE 587 Categories A and B, ESD tested to IEC 80-2 (15 KV level) EMI/RFI: Certified to FCC Part 15, Class B filtering Output voltage: 120 VRMS +/- 1% typical Output frequency: 60 Hz Output current: 3.0 Arms Output power: 300 VA/250 W maximum Output receptacles: 3 NEMA 5-15R Output waveform: Modified rectangular (smc-12/22/93)